Surface MountingNEMA 4 - NEMA 3R - Complies with U/L Std. 50Cast Iron - Hot Dipped GalvanizedThird Party Certification: UL File E 189027Standard Construction:1.Box and plain cover of cast iron.2.Stainless steel machine screws.3.Neoprene gasket.4.Larger boxes have adequate additional screws to insure tightness.Available Extras:1.Drilling only. Drilling and tapping.2.Bosses for five threads. Special gaskets.3.Mounting lugs.4.Interior mounting buttons tapped blind.5.Special cast covers.All boxes that are made in cast iron can also be made in cast aluminum – just add “AL” to the end of the part number to indicate cast aluminum.
Unit of Measure

Specifications

Type

N/A H1200

Construction

N/A cast iron

Mounting

N/A Surface

Inside Length

N/A 6 in.

Inside Width

N/A 6 in.

Inside Depth

N/A 5 in.

Approx. Weight

N/A 13.0 lbs

Approx. Wall Thickness

N/A 1/4 in.

Holes can be boss, drilled and tapped

N/A Holes can be boss, drilled and tapped by Hope Electrical Products at additional cost. Please mark up the hole locations on the attached drilling template and submit with your order to request for quote.

Stock Note

N/A If you don’t see a box size listed that you need, please inquire - we may have it. This list does not represent all of our boxes.

Note

N/A

Compare wall thickness of box with chart below to determine if wall thickness is great enough for conduit hole threads required.
If more threads required, order with Bossed, Drilled or Tapped holes.

Conduit Size No. of Threads per inch Wall Thickness Required
(NEMA VII) (NEMA IV)
5 Threads 3 1/2 Threads
1/2" - 3/4" 14 3/8" 1/4"
1" - 2" 11.5 7/16" 5/16"
2 1/2" - 4" 8 5/8" 7/16"